Click on the name of the meter to see
associated data sheets where they are
available.
Mbus Heat Meters
Approved by
Guru | Default Mbus
address | Preferred Baud
Rate | Minimum read interval on
battery
power ** | Minimum read interval on
mains
power |
Danfoss
Sonometer
1100 | ||||
Yes | Old generation meters are
mbus/0, new models are the last
two digits of the serial
number. | 2400 | 180 Seconds | 5 seconds |
Kamstrup
402 | ||||
Yes | Last 2 digits of the serial number
of the meter where the last 3
digits are less than 250 otherwise
the last 3 digits. | 2400 or 9600 | 180 Seconds | 5 seconds |
Kamstrup
403 | ||||
Yes | Last 2 digits of the serial number
of the meter where the last 3
digits are less than 250 otherwise
the last 3 digits. | 2400 or 9600 | 180 Seconds | 360
Seconds |
Landis
& Gyr UH
50 /
T550 | ||||
Yes | mbus/0 | 2400 | 900 Seconds - this
is a firmware limitation that
cannot
be shortened by Guru | 900 Seconds - this is a
firmware limitation that cannot be
shortened by Guru |
Landis
& Gyr
T230 / Ista Ultego
Ultrasmart
III | ||||
No* | mbus/0 or last 2/3
digits | 2400 | 180 Seconds | 5 seconds |
Itron CF
Echo
II | ||||
Yes | mbus/0 | 2400 | 180 Seconds | 5 seconds |
Itron CF
Ultramaxx
V | ||||
Yes | mbus/0 | 2400 | 180 Seconds | 5 seconds |
Zenner
zelcius
C5-IUF | ||||
Yes | mbus/0 | 2400 | 180 Seconds | 5 seconds |
Sonoselect
10 | ||||
Yes | 4th and
5th digits of the meter serial
number | 2400 | 180 Seconds | 5 seconds |
Kamstrup
602**/ 603 | ||||
Yes | Last 2 digits of the serial
number of the meter where the last
3 digits are less than 250
otherwise the last 3 digits | 2400 | 180 Seconds | 5 seconds |
Micronics
U1000-HM | ||||
Yes | mbus/0 | 2400 | 180 Seconds | 5 seconds |
Sonometer
1000**** | ||||
Yes | mbus/0 or
Loop 3 – 1 press
is secondary
address; 2 presses
is primary
address. | 2400 | 180 Seconds | 5 seconds |
Sontex
Superstatic
749 | ||||
Yes | mbus/0 | 2400 | 180 Seconds | 5 Seconds |
Mbus Cooling Meters
Danfoss 1100 with
cooling
tariff | ||||
Yes | Last 2
digits of the serial number with
correct flags from the mbus
frame. | 2400 | 180
Seconds | 5 seconds |
Kamstrup 403 / 603 with cooling
tariff | ||||
Yes | Last 2 digits of the serial
number of the meter where the last
3 digits are less than 250
otherwise the last 3 digits, then
include the correct mbus flags
from the mbus frame. Power &
Energy | 2400 | 180
Seconds | 5 seconds |
Kamstrup 603 cooling only | ||||
Yes | Last 2 digits of the serial
number of the meter where the last
3 digits are less than 250
otherwise the last 3 digits, then
include the correct mbus flags
from the mbus frame. Power &
Energy | 2400 | 180
Seconds | 5 seconds |
Mbus electricity meters
Inepro
PRO
1 -Mb | ||||
Yes | Last 2
digits of the serial
number with
correct flags from the
mbus
frame. | 2400 | 180
Seconds | 5 seconds |
BMeters
B21
113-100 | ||||
Yes | Mbus/0 | 2400 | 180 Seconds | 5
seconds |
Eastron
SDM230
M-Bus
V2 | ||||
Yes | Mbus/1 (Please
note only total kWh
are
displayed for meter
and
billing
purposes) | 2400 | 180
Seconds | 5
seconds |
Mbus water meters
GSD8-RFM with RFM-MB1 (install
guide) | ||||
Yes | Mbus device should be
configured before it is
used. Please see install
guide linked next to the
title. | 2400 | 180
Seconds | 5 seconds |
Dual Utility Meters
Axioma Qualsonic E3 (data sheets) | ||||
Yes | Mbus device works with two registers, one for heating and one for cooling. | 2400 | 180
Seconds | 180 seconds |
Pulse Meters
- Most pulse meters are accepted by the hub,
if however there is an abnormal length of
pulse signal then this can cause misreads
due to how the pulse is supposed to
work.
- In order to add a pulse meter, you will
need to insert the pulse rate per unit
after the pulse addressing. e.g.
pulse/0/100 for 100 pulses per unit.
- A pulse signal length can be determined by
holding a multimeter on its continuity
setting and then attaching the wires from
the meter and running consumption through
the meter, this will give an audible noise
when the pulse contact is made.
- It is highly recommended that the pulse
cable can be no longer that 15
meters due to voltage drop over the length
of a cable.
Unapproved & unsupported
Sharky
Hydrometer
775 | ||||
Meter is not
supported | | | ||
*The Landis and Gyr
T230 / Ista Ultego Smart
III is not approved on
Guru Top Units with a
serial number lower than
A0155600 at present due to
comms with the meter being
unreliable.
** For
battery-powered meters,
please confirm the maximum
polling frequency with
your meter supplier to
ensure battery life is not
adversely affected.
Setting this to 5 seconds
will severely shorten
battery
life.
***If the return
the temp becomes greater
than
the flow temp, the
Kamstrup does not flag
this up as negative
consumption. It does
however not add to the
total consumption, but it
does skew the
instantaneous demand when
viewing on the
HES.
****Mbus register
for power must be added to
the meter to send it to
the hub. If this is not
done, there is no
instantaneous demand given
to the hub. Please seek
correct documentation from
the
manufacturer.